OCV 68 DE\EL\PORV-DN Double-Interlock Pre-Action, Electro-Pneumatic Release System
Description
Electrically and pneumatically, pilot-controlled, double-interlock preaction valve, actuated by the pipeline pressure. The valve is closed in its normal, set position and opens when the pressure drops in a gas-pressurized supervisory pilot line, sensed by the relay valve, and the solenoid valve is energized. An emergency manual release valve is fitted as standard. Also available with manual reset: DE\ EL\PORV-DN-MR.
Certification & Compliance
UL Listed under VLFT category
ABS Type Approval
Lloyd’s Register Approval
ANSI FCI 70-2 Class VI seat leakage class
Fire tested to EN ISO 6182-5:2006 (2”-6” only)
– High pressure (PN25/375psi), high flow systems
– Automatic or manual emergency actuation
– Industrial & commercial fire suppression
– Hazardous, flammable & explosion classified area fire suppression
– Superior design featuring exceptionally low-pressure losses at high flow rates
– Low lifelong maintenance costs due to straightforward design
– Applicable for water, seawater & foam